Call 08044920295 90% Response Rate
Send Enquiry
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI810 / 3BSE008516R1 |
The AI810 Analog Input Module has 8 channels. Each channel can be either a voltage or current input. The current input is able to handle a short circuit to the transmitter supply at least 30 V d.c without damage. Current limiting is performed with a PTC resistor. The input resistance of the current input is 250 ohm, PTC included.
The voltage input is able to withstand an over or undervoltage of at least 30 V d.c. Input resistance is 290k ohm. Transmitter supply can be connected to L1+, L1- and/or L2+, L2-.
Features and benefitsArticle number | 3BSE008516R1 |
Type | Analog Input |
Signal specification | 0..20mA, 4..20mA, 0..10V, 2..10V |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 12 bit |
Input impedance | 290 kΩ (voltage input) 230 - 275 kΩ (current input) |
Isolation | Groupwise isolated from ground |
Under/over range | -5% / +15% |
Error | Max. 0.1% |
Temperature drift | Voltage: Typ. 70 ppm/°C Max. 100 ppm/°C; Current: Typ. 50 ppm/°C Max. 80 ppm/°C |
Input filter (rise time 0-90%) | 140 ms |
Update cycle time | 8 ms |
Current limiting | Transmitter power can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Max input voltage (non destructive) | 30 V d.c. |
NMRR, 50Hz, 60Hz | > 40 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 1.5 W |
Current consumption +5 V Modulebus | 70 mA |
Current consumption +24 V Modulebus | 40 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI815 / 3BSE052604R1 |
The AI815 Analog Input Module has 8 channels. The modules can be configured for voltage or current inputs. Current and voltage signals cannot be mixed on the same I/O module. The voltage and current input is able to withstand an overvoltage or undervoltage of at least 11 V d.c.
The input resistance for voltage input is greater than 10 M ohm, and the input resistance for current input is 250 ohm. The module distributes the external HART compatible transmitter supply to each channel. This adds a simple connection to distribute the supply to 2-wire or 3-wire transmitters. The transmitter power is supervised and current limited. If an external power supply is used for feeding HART transmitters, the power supply must be HART compatible.
Features and benefitsArticle number | 3BSE052604R1 |
Type | Analog Input |
Signal specification | 0..20 mA, 4..20 mA, 0..5 V, 1..5 V |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | Yes |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 12 bit |
Input impedance | 10 MΩ (voltage input) 250 Ω (current input) |
Isolation | Groupwise isolated from ground |
Under/over range | 0 / +15% (0..20 mA, 0..5 V), -12.5% / +15% (4..20 mA, 1..5 V) |
Error | Max. 0.1% |
Temperature drift | Max. 50 ppm/°C |
Input filter (rise time 0-90%) | 290 ms |
Update cycle time | 10 ms |
Current limiting | Built in current limited transmitter power |
Maximum field cable length | 600 meters (656 yards) |
NMRR, 50Hz, 60Hz | > 40 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 3.5 W |
Current consumption +5 V Modulebus | 100 mA |
Current consumption +24 V Modulebus | 50 mA |
Current consumption +24 V external | Max. 265 mA (22 mA + 1.32 * transmitter current) |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI825 / 3BSE036456R1 |
The AI825 Analog Input Module has 4 individually galvanic isolated, bipolar current/voltage inputs. Each channel can be either a voltage or current input.
The module has a direct current input that withstand up to 6.3 V and a over voltage protected current input that withstand up to +30 V d.c. The current is limited by a PTC resistor.
Power to the input stages is converted from the 24 V on the ModuleBus.
Features and benefitsArticle number | 3BSE036456R1 |
Type | Analog Input |
Signal specification | -20..+20 mA, 0(4)..20 mA, -10..+10 V, 0(2)..10V |
Number of channels | 4 |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 14 bit plus sign |
Input impedance | 10 MΩ (voltage input) 50 Ω (current input) |
Isolation | Individually isolated, channel-to-channel and to circuit common |
Under/over range | ± 15% |
Error | Max. 0.1% |
Temperature drift | Max. 47 ppm/°C (0..10V), Max. 34 ppm/°C (±10V), Max. 78 ppm/°C (0..20mA), Max. 57 ppm/°C (±20mA) |
Input filter (rise time 0-90%) | 115 ms (voltage input), 130 ms (current input) |
Update cycle time | < 10ms |
Maximum field cable length | 600 meters (656 yards) |
CMRR, 50Hz, 60Hz | 120 dB |
NMRR, 50Hz, 60Hz | > 40 dB at 50 Hz, >55 dB at 60 Hz |
Rated insulation voltage | 250 V |
Dielectric test voltage | 1900 V d.c. ch-ch, 3250 V d.c. ch-ground/system, |
Power dissipation | Typ. 2.5 W, Max. 3.2 W |
Current consumption +5 V Modulebus | Typ. 70 mA, Max. 100 mA |
Current consumption +24 V Modulebus | Typ. 90 mA, Max. 110 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI830A / 3BSE040662R1 |
The AI830/AI830A RTD Input Module has 8 channels for measurement of temperature with resistive elements (RTDs). With 3-wire connections. All the RTDs must be isolated from ground.
The AI830/AI830A can be used with Pt100, Cu10, Ni100, Ni120 or resistive sensors. Linearization and conversion of the temperature to Centigrade or Fahrenheit is performed on the module.
Every channel can be individually configured. The MainsFreq parameter is used to set mains frequency filter cycle time. This will give a notch filter at the frequency specified (50 Hz or 60 Hz).
Features and benefitsArticle number | 3BSE040662R1 |
Type | Analog Input |
Signal specification | 3-wire RTD: Pt100, Cu10, NI100, Ni120 and resistive potentiometer |
Number of channels | 8 |
Signal type | See table in S800 Modules and Termination Units, 3BSE020924 |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | See table in S800 Modules and Termination Units, 3BSE020924-xxx |
Isolation | Groupwise isolated from ground |
Error | Error dependent of the field cable resistance: Rerr = R* (0.005 + ∆R/100) Terr°C = Rerr / (R0 * TCR) Terr°F = Terr°C * 1.8 |
Temperature drift | See table in S800 Modules and Termination Units, 3BSE020924-xxx |
Update cycle time | 150 + 95 * (number of active channels) ms |
CMRR, 50Hz, 60Hz | >120 dB (at 10Ω load) |
NMRR, 50Hz, 60Hz | >60 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 1.6 W |
Current consumption +5 V Modulebus | 70 mA |
Current consumption +24 V Modulebus | 50 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI835A / 3BSE051306R1 |
The AI835/AI835A provides 8 differential input channels for Thermocouple/mV measurements. Measurement ranges configurable per channel are: -30 mV to +75 mV linear, or TC Types B, C, E, J, K, N, R, S and T, for AI835A also D, L and U.
One of the channels (Channel 8) may be configured for “Cold Junction” (ambient) temperature measurements, thus serving as CJ-channel for Ch. 1...7. The junction temperature may be measured locally on the MTUs screw terminals, or on a connection unit distant form the device.
Alternatively, a fix junction temperature for the module may be set by the user (as parameter) or for AI835A also from the application. Channel 8 may be used in the same manner as Ch. 1...7 when no CJ-temperature measurement is needed.
Features and benefitsArticle number | 3BSE051306R1 |
Type | Analog Input |
Signal specification | -30..75 mV linear; TC types B, C, D, E, J, K, L, N, R, S, T and U |
Number of channels | 8 |
Signal type | See table in S800 Modules and Termination Units, 3BSE020924 |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 15 bits |
Input impedance | > 1 MΩ |
Isolation | Groupwise isolated from ground |
Error | Max. 0.1% |
Temperature drift | Typ. 5 ppm/°C, Max. 7 ppm/°C |
Update cycle time | 280 + 80 * (number of active channels) ms at 50 Hz; 250 + 70 * (number of active channels) ms at 60 Hz |
Maximum field cable length | 600 meters (656 yards) |
CMRR, 50Hz, 60Hz | 120 dB |
NMRR, 50Hz, 60Hz | > 60 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 1.6 W |
Current consumption +5 V Modulebus | 75 mA |
Current consumption +24 V Modulebus | 50 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI843 / 3BSE028925R1 |
The AI843 Thermocouple/mV Input Module provides 8 differential input channels for Thermocouple/mV measurements. Measurement ranges configurable per channel are: -30 mV to +75 mV linear, or TC Types B, C, E, J, K, L, N, R, S, T and U. A separate Pt100 channel is used for “Cold Junction” (ambient) temperature measurements, thus serving as CJ-channel for Ch. 1...8.
The junction temperature may be measured locally on the MTUs screw terminals, or on a connection unit distant form the device. Alternatively, a fix junction temperature for the module may be set by the user (as parameter) or a junction temperature set by the application.
Features and benefitsArticle number | 3BSE028925R1 |
Type | Analog Input |
Signal specification | -30..75 mVlinear, TC types B, C, E, J, K, L, N, R, S, T and U |
Number of channels | 8 |
Signal type | See table |
HART | No |
SOE | No |
Redundancy | Yes |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 16 bits |
Input impedance | > 1 MΩ |
Isolation | Groupwise isolated from ground |
Error | Max. 0.1% |
Temperature drift | Typ. 10 ppm/°C, Max. 25 ppm/°C |
Input filter (rise time 0-90%) | 1.1 kHz |
Update cycle time | 320 + 80 * (no of active channels) ms at 50 Hz 267 + 67 * (no of active channels) at 60 Hz |
Maximum field cable length | 600 meters (656 yards) or max. 500 Ω |
CMRR, 50Hz, 60Hz | 100 dB |
NMRR, 50Hz, 60Hz | > 40 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 1.5 W |
Current consumption +5 V Modulebus | 60 mA |
Current consumption +24 V Modulebus | 50 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI845 / 3BSE023675R1 |
The AI845 Analog Input Module for single or redundant applications. The module has 8 channels. Each channel can be either a voltage or current input when MTU TU844 or TU845 is used, when other MTUs are used all channels become voltage or current inputs.
The voltage and current input is able to withstand an overvoltage or undervoltage of at least 11 V d.c. The input resistance for voltage input is greater than 10 M ohm and the input resistance for current input is 250 ohm.
The module distributes the external HART compatible transmitter supply to each channel. This adds a simple connection to distribute the supply to 2-wire or 3-wire transmitters. The transmitter power is supervised and current limited.
Features and benefitsArticle number | 3BSE023675R1 |
Type | Analog Input |
Signal specification | 0..20mA, 4..20 mA, 0..5 V, 1..5 V |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | Yes |
SOE | No |
Redundancy | Yes |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 12 bit |
Input impedance | 10 MΩ (voltage input) 250 Ω (current input) |
Isolation | Groupwise isolated from ground |
Under/over range | 0 / +15% (0..20 mA, 0..5 V), -12.5% / +15% (4..20 mA, 1..5 V) |
Error | Max. 0.1% |
Temperature drift | Max. 50 ppm/°C |
Input filter (rise time 0-90%) | 290 ms |
Update cycle time | 10 ms |
Current limiting | Built in current limited transmitter power |
Maximum field cable length | 600 meters (656 yards) |
Max input voltage (non destructive) | 11 V d.c. |
NMRR, 50Hz, 60Hz | > 40 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 3.5 W |
Current consumption +5 V Modulebus | 100 mA |
Current consumption +24 V Modulebus | 50 mA |
Current consumption +24 V external | Max. 265 mA (22 mA + transmitter current * 1.32) |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AO801 / 3BSE020514R1 |
The AO801 Analog Output Module has 8 unipolar analog output channels. The module performs selfdiagnostic cyclically. A low internal power supply sets the module in INIT state (no signal from the module).
Features and benefitsArticle number | 3BSE020514R1 |
Type | Analog Output |
Signal specification | 0... 20 mA, 4...20 mA |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800L |
Resolution | 12 bit |
Isolation | Groupwise isolated from ground |
Under/over range | - / +15% |
Output load | Max 850 Ω |
Error | 0,1 % |
Temperature drift | Typ 30 ppm/°C, Max 50 ppm/°C |
Rise Time | 10 µs |
Update cycle time | 1 ms |
Current limiting | Short circuit proof current limited output |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 3.8 W |
Current consumption +5 V Modulebus | 70 mA |
Current consumption +24 V Modulebus | - |
Current consumption +24 V external | 200 mA |
Supported wire size | Solid: 0.05-2.5 mm², 30-12 AWG Stranded: 0.05-1.5 mm², 30-12 AWG Recommended torque: 0.5-0.6 Nm Stripping length 6-7.5mm, 0.24-0.30 inch |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AO810V2 / 3BSE038415R1 |
The AO810/AO810V2 Analog Output Module has 8 unipolar analog output channels. To supervise the communication to the D/A-converters the serial data is read back and verified. The opencircuit diagnostic is received during the readback. The module performs self-diagnostic cyclically. The module diagnostics includes process power supply supervision, which is reported when supply voltage to output circuitry is to low. The error is reported as a channel error. The channel diagnostic includes fault detection of the channel (only reported on active channels). The error is reported if the output current is less than the output set value and the output set value is greater than 1 mA.
Features and benefitsArticle number | 3BSE038415R1 |
Type | Analog Output |
Signal specification | 0..20 mA, 4..20 mA |
Number of channels | 8 |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 14 bit |
Isolation | Groupwise isolated from ground |
Under/over range | - / +15% |
Output load | ≤ 500 Ω (supply connected to L1+ only) 250 - 850 Ω (with supply connected L2+ only) |
Error | Max. 0.1% at 0 - 500 ohms (current) |
Temperature drift | Typ. 30 ppm/°C, Max 60 ppm/°C |
Rise Time | 0.35 ms (PL = 500 Ω) |
Update cycle time | ≤ 2ms |
Current limiting | Short circuit proof current limited output |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 2.3 W |
Current consumption +5 V Modulebus | Max 70 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 245 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AO820 / 3BSE008546R1 |
The AO820 Analog Output Module has 4 bipolar analog output channels. The choice of current or voltage output is configurable for each channel. There are separate sets of terminals for voltage and current outputs, and it is up to the user to wire outputs properly. The only differences between current or voltage channel configuration is in software settings.
To supervise the communication to the A/D-converters the output data is read back and verified. The opencircuit diagnostics are read continuously as well. The process voltage supervision input give channel error signals if the voltage disappears. The error signal can be read via the ModuleBus.
Features and benefitsArticle number | 3BSE008546R1 |
Type | Analog Output |
Signal specification | -20 mA...+20 mA, 0...20 mA, 4...20 mA, -10 V...+10 V, 0...10 V, 2...10 V |
Number of channels | 4 |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 12 bits including sign |
Isolation | Individually isolated - channel-to-channel and channel to circuit common |
Under/over range | ±15% |
Output load | ≤ 550 Ω ≥ 5 kΩ (voltage output) |
Error | Max. 0.1% (voltage); Typ. 0.1% at 250 ohms, Max 0,15% (current) |
Temperature drift | Max 90 ppm/°C |
Rise Time | < 0.7 ms |
Update cycle time | ≤ 1.5 ms |
Current limiting | Short circuit proof current limited output |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 6 W |
Current consumption +5 V Modulebus | Max 100 mA |
Current consumption +24 V Modulebus | Max 260 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AO845A / 3BSE045584R1 |
The AO845/AO845A Analog Output Module for single or redundant applications has 8 unipolar analog output channels. The module performs self-diagnostic cyclically. Module diagnostics include:
Article number | 3BSE045584R1 |
Type | Analog Output |
Signal specification | 4..20 mA |
Number of channels | 8 |
HART | Yes |
SOE | No |
Redundancy | Yes |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 12 bit |
Isolation | Groupwise isolated from ground |
Under/over range | -12.5% / +15% |
Output load | Max 750 Ω |
Error | Max. 0.1% |
Temperature drift | Max. 50 ppm/°C |
Rise Time | Output filter: Disable 23 ms, Enable max 4 mA / 12.5 ms |
Input filter (rise time 0-90%) | 23 ms (0-90%), max 4 mA / 12.5 ms |
Update cycle time | 10 ms |
Current limiting | Short circuit proof current limited output |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 3.5 W |
Current consumption +5 V Modulebus | Max. 125 mA |
Current consumption +24 V external | 218 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DI801 / 3BSE020508R1 |
The DI801 is a 16 channel 24 V digital input module for the S800 I/O. This module has 16 digital inputs. The input voltage range is 18 to 30 volt d.c. and the input current is 6 mA at 24 V. The inputs are in one isolated group with sixteen channels and channel number sixteen can be used for voltage supervision input in the group. Every input channel consists of current limiting components, EMC protection components, input state indication LED and optical isolation barrier.
Features and benefitsArticle number | 3BSE020508R1 |
Type | Digital Input |
Signal specification | 24V d.c. |
Number of channels | 16 |
Signal type | Current sinking |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800L |
Input voltage range, "0" | -30 .. +5 V |
Input voltage range, "1" | 15 .. 30 V |
Input impedance | 3.5 kΩ |
Isolation | Groupwise isolated from ground |
Filter times (digital, selectable) | 2, 4, 8, 16 ms |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V |
Power dissipation | Typ 2.2 W |
Current consumption +5 V Modulebus | 70 mA |
Current consumption +24 V Modulebus | 0 |
Supported wire size | Solid: 0.05-2.5 mm², 30-12 AWG Stranded: 0.05-1.5 mm², 30-12 AWG Recommended torque: 0.5-0.6 Nm Stripping length 6-7.5mm, 0.24-0.30 inch |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DI818 / 3BSE069052R1 |
This module has 32 digital inputs. The input voltage range is 18 to 30 volt d.c. and the input current is 4.3mA at 24 V. The inputs are divided into two individually isolated groups with 16 channels and one voltage supervision input in each group. Every input channel consists of current limiting components, EMC protection components, input state indication LED and optical isolation barrier. The process voltage supervision input give channel error signals if the voltage disappears. The error signal can be read via the ModuleBus.
Features and benefitsArticle number | 3BSE069052R1 |
Type | Digital Input |
Signal specification | 24 V d.c. |
Number of channels | 32 |
Signal type | Current sinking |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Input voltage range, "0" | -30 .. +5 V |
Input voltage range, "1" | 11 .. 30 V |
Input impedance | 5.6 kΩ |
Isolation | Groupwise isolated from ground, groups of 16 channels |
Filter times (digital, selectable) | 2, 4, 8, 16 ms |
Current limiting | Sensor power can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 3.1 W |
Current consumption +5 V Modulebus | 70 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 25 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DI820 / 3BSE008512R1 |
This module has 8 digital inputs. The a.c. input voltage range is 77 - 130 volt and the input current is 10 mA at 120 V a.c. The d.c. input range is 75 - 145 V and the input current is 2.8 mA at 110 V. The inputs are individually isolated.
Every input channel consists of current limiting components, EMC protection components, input state indication LED, optical isolation barrier and an analog filter (6 ms). Channel 1 can be used as voltage supervision input for channels 2 - 4, and channel 8 can be used as voltage supervision input for channels 5 - 7.
If the voltage connected to channel 1 or 8 disappears, the error inputs are activated and the Warning LED turns on. The error signal can be read from the ModuleBus.
Features and benefitsArticle number | 3BSE008512R1 |
Type | Digital Input |
Signal specification | 120 V a.c. / 110 V d.c. |
Number of channels | 8 |
Signal type | Current sinking |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Input voltage range, "0" | 0..30 V a.c., 0..20 V d.c. |
Input voltage range, "1" | 77..130 V a.c., 75..145 V d.c. |
Input impedance | 12 kΩ (a.c.) / 39 kΩ (d.c.) |
Isolation | Individually isolated channels |
Filter times (digital, selectable) | 2, 4, 8, 16 ms |
Input frequencey range | 47..63 Hz |
Analog filter On/Off delay | 5 / 18 ms |
Current limiting | Sensor power can be current limited by the MTU |
Maximum field cable length | 200 meters (219 yards) 100 pF/m for a.c., 600 meters (656 yards) for d.c. |
Rated insulation voltage | 250 V |
Dielectric test voltage | 2000 V a.c. |
Power dissipation | Typ. 2.8 W |
Current consumption +5 V Modulebus | 50 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DI830 / 3BSE013210R1 |
The DI830 is a 16 channel 24 V d.c. digital input module for the S800 I/O. The input voltage range is 18 to 30 V d.c. and the input current is 6 mA at 24 V d.c. Each input channel consists of current limiting components, EMC protection components, input state indication LED and optical isolation barrier. The module cyclically performs self-diagnostics. Module diagnostics include:
The input signals can be digitally filtered. The filter time can be set in the range 0 to 100 ms. This means that pulses shorter than the filter time are filtered out and pulses longer than specified filter time get through the filter.
Features and benefitsArticle number | 3BSE013210R1 |
Type | Digital Input |
Signal specification | 24 V d.c. |
Number of channels | 16 |
Signal type | Current sinking |
HART | No |
SOE | Yes |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Input voltage range, "0" | -30..+5 V |
Input voltage range, "1" | 13..30 V |
Input impedance | 3.2 kΩ |
Isolation | Groupwise isolated from ground |
Filter times (digital, selectable) | 0...100 ms |
Current limiting | Sensor power can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Event recording accuracy | -0.3 ms...+0.7 ms |
Event recording resolution | 0.4 ms |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 2.3 W |
Current consumption +5 V Modulebus | Typ. 100 mA, Max 120 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU842 / 3BSE020850R1 |
The TU842 MTU can have up to 16 I/O channels and 2+2 process voltage connections. Each channel has two I/O connections and one ZP connection. The maximum rated voltage is 50 V and maximum rated current is 3 A per channel.
The MTU distributes the two ModuleBuses to each I/O module and to the next MTU. It also generates the correct address to the I/O modules by shifting the outgoing position signals to the next MTU.
The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail.
Four mechanical keys, two for each I/O module, are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and benefitsArticle number | 3BSE020850R1 |
Type | Redundant |
Connection | Terminal block |
Channels | 16 |
Voltage | 50 V |
Mounting | Horizontal |
Mounting detail | 55 º (131 °F) |
Use with I/O | AI843, AO845, AO845A, DI840, DI880, DO840, DO880 and DP840 |
Process connections | 56 up to 16 I/O channels (2 terminals per channel), 4 Process power, 20 Process power (0 V) |
Single/redundant I/O | Redundant |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU837V1 / 3BSE013238R1 |
The TU837V1 MTU can have up to 8 I/O channels. The maximum rated voltage is 250 V and maximum rated current is 3 A per channel. The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU.
The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail. The latch can be released with a screwdriver. Two mechanical keys are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and benefitsArticle number | 3BSE013238R1 |
Type | Extended |
Connection | Terminal block |
Channels | 8 |
Voltage | 250 V |
Mounting | Both directions |
Mounting detail | 55 ºC (131 °F) |
Use with I/O | DO820, and DO821 |
Process connections | 28 up to 8 I/O channels (2 terminals per channel) 2 x 6 power common terminals |
Single/redundant I/O | Single |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU833 / 3BSE038726R1 |
The TU833 MTU can have up to 16 I/O channels and two process voltage connections. Each channel has two I/O connections and one ZP connection. The process voltage can be connected to two individually isolated groups. Each group has a 6.3 A fuse. The maximum rated voltage is 50 V and maximum rated current is 2 A per channel. It is recommended that the fuse rating be chosen to meet the applications needs, see S800 I/O Getting Started chapter Power and Cooling.
The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU.
The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail.
Features and benefitsArticle number | 3BSE038726R1 |
Type | Extended |
Connection | Crimp Snap-in connector |
Channels | 16 |
Voltage | 50 V |
Mounting | Both directions |
Mounting detail | 55 ºC (131 °F) |
Use with I/O | AI810, AI815, AI820, AI830, AI830A, AI835, AI835A, AI843, AI845, AO810, AO810V2, AO815, AO820, AO845, AO845A, DI810, DI811, DI814, DI830, DI831, DI840, DI880, DI885, DO810, DO814, DO815, DO840, DO880, DP820 and DP840 |
Process connections | 56 up to 16 I/O channels (2 terminals per channel) 4 Process power 6.3 A 10 x 2 Process power (0 V) |
Single/redundant I/O | Single |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DI840 / 3BSE020836R1 |
The DI840 is a 16 channel 24 V d.c. digital input module for single or redundant applications. The input voltage range is 18 to 30 V d.c. and the input current is 7 mA at 24 V d.c. Each input channel consists of current limiting components, EMC protection components, input state indication LED and optical isolation barrier.
The transducer power is supervised and current limited; one output per two input channels. The Sequence of Event function (SOE) can collect events with a resolution of 1 ms. The event queue can contain up to 257 events. The function includes a Shutter filter for filtering out unwanted events.
Features and benefitsArticle number | 3BSE020836R1 |
Type | Digital Input |
Signal specification | 24 V d.c. |
Number of channels | 16 |
Signal type | Current sinking |
HART | No |
SOE | Yes |
Redundancy | Yes |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Input voltage range, "0" | -30..+5 V |
Input voltage range, "1" | 11..30 V |
Input impedance | 3.3 kΩ |
Isolation | Groupwise isolated from ground |
Filter times (digital, selectable) | 0 to 127 ms |
Current limiting | Built in current limited sensor power |
Maximum field cable length | 600 meters (656 yards) |
Event recording accuracy | 0 ms / +1.3 ms |
Event recording resolution | 1 ms |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 2.7 W |
Current consumption +5 V Modulebus | 100 mA |
Current consumption +24 V external | 15 mA + transducer power, Max 335 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DO820 / 3BSE008514R1 |
The DO820 is an 8 channel 230 V a.c./d.c. relay (NO) output module for the S800 I/O. The maximum output voltage is 250 V a.c./d.c. and the maximum continuous output current is 3 A. All outputs are individually isolated. Each output channel consists of optical isolation barrier, output state indication LED, relay driver, relay and EMC protection components. The relay supply voltage supervision, derived from the 24 V distributed on the ModuleBus, gives an error signal if the voltage disappears, and the Warning LED turns on. The error signal can be read through the ModuleBus. This supervision can be enabled/disabled with a parameter.
Features and benefitsArticle number | 3BSE008514R1 |
Type | Digital Output |
Signal specification | 230 V a.c. / d.c. (5 - 250 V a.c./d.c.), 3 A |
Number of channels | 8 |
Signal type | Relay (NO) |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Isolation | Individually isolated, channel-to-channel and to circuit common |
Current limiting | Can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Event recording accuracy | -0 ms / +1.3 ms |
Rated insulation voltage | 250 V |
Dielectric test voltage | 2000 V a.c. |
Power dissipation | Typ. 2.9 W |
Current consumption +5 V Modulebus | 60 mA |
Current consumption +24 V Modulebus | 140 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DO828 / 3BSE069055R1 |
The DO828 is an 16 channel 125V d.c. / 250V a.c. relay output module for the S800 I/O. The maximum output voltage is 125V d.c. / 250V a.c. and the maximum continuous output current is 2A. All outputs are individually isolated.
Each output channel consists of optical isolation barrier, output state indication LED, relay driver, relay and EMC protection components.
The relay supply voltage supervision, derived from the 12 V distributed on the ModuleBus, gives an error signal if the voltage disappears, and the Warning LED turns on. The error signal can be read through the ModuleBus. This supervision can be enabled/disabled with a parameter.
Features and benefitsArticle number | 3BSE069055R1 |
Type | Digital Output |
Signal specification | 125 V d.c. / 250 V a.c., (5 - 125 V d.c. / 5 - 250 V a.c.), 2 A |
Number of channels | 16 |
Signal type | Relay (NO) |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Isolation | Individually isolated, channel-to-channel and to circuit common |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 250 V |
Dielectric test voltage | 2000 V a.c. |
Power dissipation | Typ. 3.5 W |
Current consumption +5 V Modulebus | 45 mA |
Current consumption +24 V Modulebus | 80 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DO840 / 3BSE020838R1 |
This module has 16 digital outputs. The maximum continuous output current per channel is 0.5 A. The outputs are current limited and protected against over temperature. The outputs are divided into two groups with eight output channels and one voltage supervision input in each group. Each output channel consists of a current limited and over temperature protected high side driver, EMC protection components, inductive load suppression, output state indication LED and optical isolation barrier.
Features and benefitsArticle number | 3BSE020838R1 |
Type | Digital Output |
Signal specification | 24 V d.c. (19.2 - 32 V d.c.), 0.5 A |
Number of channels | 16 |
Signal type | Current sourcing, current limiting |
HART | No |
SOE | No |
Redundancy | Yes |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Isolation | Groupwise isolated from ground |
Current limiting | Short circuit proof current limited output |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 4.3 W |
Current consumption +5 V Modulebus | 130 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 200 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU805K01 / 3BSE035990R1 |
The TU805K01 is a kit consisting of 10 pcs TU805. TU805 is a 16-channel 50 V terminal unit for the S800 I/O modules DI801 and DO801. The Terminal Unit is a passive unit for the distribution of external process power.
Features and benefitsArticle number | 3BSE035990R1 |
Connection | Terminal block |
Channels | 16 |
Voltage | 50 V |
Use with I/O | DI801, DO801 |
Process connections | 2 x 2 Process power terminals 2 x 16 Process power distribution terminals |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU811V1 / 3BSE013231R1 |
The TU811V1 is a 8 channel 250 V compact module termination unit (MTU) for the S800 I/O. The MTU is a passive unit used for connection of the field wiring to the I/O modules. It also contains a part of the ModuleBus.
The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU.
Two mechanical keys are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and benefitsArticle number | 3BSE013231R1 |
Type | Compact |
Connection | Terminal block |
Channels | 8 |
Voltage | 250 V |
Mounting | Both directions |
Mounting detail | Horizontal 55 Cº (131 °F) Vertical 40 ºC (104 °F) |
Use with I/O | DI820, DI821, DO820, and DO821 |
Single/redundant I/O | Single |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU845 / 3BSE021447R1 |
The TU845 MTU can have up to 8 I/O channels and 2+2 process voltage connections. Each channel has two I/O connections and one ZP connection. Input signals are connected via individual shunt sticks, TY801. The shunt stick is used to choose between voltage and current input. The maximum rated voltage is 50 V and maximum rated current is 2 A per channel.
The MTU distributes the two ModuleBuses, one to each I/O module and to the next MTU. It also generates the correct address to the I/O modules by shifting the outgoing position signals to the next MTU. It has a mechanical latch that locks the MTU to the DIN rail.
Four mechanical keys, two for each I/O module, are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and benefitsArticle number | 3BSE021447R1 |
Type | Redundant |
Connection | Terminal block |
Channels | 8 |
Voltage | 50 V |
Mounting | Vertical |
Mounting detail | 55 º (131 °F) |
Use with I/O | AI845, AI880, AI880A and DP840 |
Process connections | 40 up to 8 I/O channels (2 terminals per channel) 4 Process power 20 Process power (0 V) |
Single/redundant I/O | Redundant |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU831V1 / 3BSE013235R1 |
The TU831V1 MTU can have up to 8 I/O channels. The maximum rated voltage is 250 V and maximum rated current is 3 A per channel.
The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU. The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail.
Features and benefitsArticle number | 3BSE013235R1 |
Type | Extended |
Connection | Terminal block |
Channels | 8 |
Voltage | 250 V |
Mounting | Both directions |
Mounting detail | 55 ºC (131 °F) |
Use with I/O | DI820, DI821, DO820, and DO821 |
Process connections | 16 up to 8 I/O channels (2 terminals per channel) |
Single/redundant I/O | Single |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU844 / 3BSE021445R1 |
The TU844 MTU can have up to 8 I/O channels and 2+2 process voltage connections. Each channel has two I/O connections and one ZP connection. Input signals are connected via individual shunt sticks, TY801. The shunt stick is used to choose between voltage and current input. The maximum rated voltage is 50 V and maximum rated current is 2 A per channel.
The MTU distributes the two ModuleBuses, one to each I/O module and to the next MTU. It also generates the correct address to the I/O modules by shifting the outgoing position signals to the next MTU.
The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail.
Four mechanical keys, two for each I/O module, are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Article number | 3BSE021445R1 |
Type | Redundant |
Connection | Terminal block |
Channels | 8 |
Voltage | 50 V |
Mounting | Horizontal |
Mounting detail | 55 º (131 °F) |
Use with I/O | AI845, AI880, AI880A and DP840 |
Process connections | 40 up to 8 I/O channels (2 terminals per channel) 4 Process power 20 Process power (0 V) |
Single/redundant I/O | Redundant |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU843 / 3BSE021443R1 |
The TU843 MTU can have up to 16 I/O channels and 2+2 process voltage connections. Each channel has two I/O connections and one ZP connection. The maximum rated voltage is 50 V and maximum rated current is 3 A per channel.
The MTU distributes the two ModuleBuses, one to each the I/O module and to the next MTU. It also generates the correct address to the I/O modules by shifting the outgoing position signals to the next MTU.
The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail.
Four mechanical keys, two for each module, are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Article number | 3BSE021443R1 |
Type | Redundant |
Connection | Terminal block |
Channels | 16 |
Voltage | 50 V |
Mounting | Vertical |
Mounting detail | 55 º (131 °F) |
Use with I/O | AI843, AO845, AO845A, DI840, DI880, DO840, DO880 and DP840 |
Process connections | 56 up to 16 I/O channels (2 terminals per channel) 4 Process power 20 Process power (0 V) |
Single/redundant I/O | Redundant |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DO818 / 3BSE069053R1 |
The DO818 is a 32 channel 24 V digital output module for the S800 I/O. This module has 16 digital outputs. The output voltage range is 12 to 32 volt and the maximum continuous output current is 0.5 A. The outputs are protected against short circuits, over voltage and over temperature. The outputs are divided into two individually isolated groups with 16 output channels and one voltage supervision input in each group. Each output channel consists of a short circuit and over temperature protected high side driver, EMC protection components, inductive load suppression, output state indication LED and optical isolation barrier. The process voltage supervision input give channel error signals if the voltage disappears. The error signal can be read through the ModuleBus.
Features and benefitsArticle number | 3BSE069053R1 |
Type | Digital Output |
Signal specification | 24 V d.c. (12 - 32 V d.c.), 0.5 A |
Number of channels | 32 |
Signal type | Current sourcing, current limiting |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Isolation | Groupwise isolated from ground |
Output load | < 0.32 Ω |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ 2.8 W |
Current consumption +5 V Modulebus | Typ 70 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 40 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DO821 / 3BSE013250R1 |
The DO821 is an 8 channel 230 V a.c./d.c. relay (NC) output module for the S800 I/O. The maximum output voltage is 250 V a.c. and the maximum continuous output current is 3 A. All outputs are individually isolated. Each output channel consists of optical isolation barrier, output state indication LED, relay driver, relay and EMC protection components. The relay supply voltage supervision, derived from the 24 V distributed on the ModuleBus, gives an error signal if the voltage disappears, and the Warning LED turns on. The error signal can be read via the ModuleBus. This supervision can be enabled/disabled with a parameter.
Features and benefitsArticle number | 3BSE013250R1 |
Type | Digital Output |
Signal specification | 230 V a.c./d.c. (5-250 V a.c./d.c.), 3 A |
Number of channels | 8 |
Signal type | Relay (NC) |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Isolation | Individually isolated, channel-to-channel and to circuit common |
Current limiting | Can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 250 V |
Dielectric test voltage | 2000 V a.c. |
Power dissipation | Typ. 2.9 W |
Current consumption +5 V Modulebus | 60 mA |
Current consumption +24 V Modulebus | 140 mA |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | COUNTER MODULE |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DP840 / 3BSE028926R1 |
The DP840 module consists of 8 identical independent channels. Each channel can be used for pulse count or frequency (speed) measurement, maximum 20 kHz. The inputs can also be read as DI signals. Each channel has a configurable input filter. The module perform self-diagnostics cyclically. With advanced diagnostics, for single or redundant applications. Interface for NAMUR, 12 V and 24 V. The input can be read as digital input signals.
Use DP840 with Module Termination Units TU810V1, TU812V1, TU814V1, TU830V1, TU833.
Features and benefitsArticle number | 3BSE028926R1 |
Type | Pulse counter |
Signal specification | 24 V d.c. (19.2 - 32 V d.c.) |
Number of channels | 8 |
HART | No |
SOE | No |
Redundancy | Yes |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU810V1 / 3BSE013230R1 |
The TU810/TU810V1 is a 16 channel 50 V compact module termination unit (MTU) for the S800 I/O. The MTU is a passive unit used for connection of the field wiring to the I/O modules. It also contains a part of the ModuleBus.
The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU.
Two mechanical keys are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and benefitsArticle number | 3BSE013230R1 |
Type | Compact |
Connection | Terminal block |
Channels | 16 |
Voltage | 50 V |
Mounting | Both directions |
Mounting detail | Horizontal 55 ºC (131 °F) Vertical 40 ºC (104 °F) |
Use with I/O | AI810, AI815, AI820, AI830, AI830A, AI835, AI835A, AI845, AO810, AO810V2, AO815, AO820, AO845, AO845A, DI810, DI811, DI814, DI830, DI831, DI840, DI880, DI885, DO810, DO814, DO815, DO840, DO880, DP820, DP840 |
Process connections | 2 x 2 Process power, 5 x 2 Process power (0 V) |
Single/redundant I/O | Single |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | MTU |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | TU818 / 3BSE069209R1 |
The TU818 is a 32 channel 50 V compact module termination unit (MTU) for the S800 I/O. The MTU is a passive unit used for connection of the field wiring to the I/O modules. It also contains a part of the ModuleBus.
The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU.
Two mechanical keys are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and benefitsArticle number | 3BSE069209R1 |
Type | Compact |
Connection | Terminal block |
Channels | 32 |
Voltage | 50 V |
Mounting | Both directions |
Mounting detail | Horizontal 55 ºC (131 °F) Vertical 40 ºC (104 °F) |
Use with I/O | AI810, AI815, AI835A, AI843, AI845, DI810, DI811, DI818, DI830, DI831, DI840, DI880, DI885, DO818, DP840 |
Process connections | 40 pole screw terminal |
Single/redundant I/O | Single |
Additional Information:
View Complete details
Product Brochure
Number of Channels | 2 |
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Model Name/Number | DO815 |
Output Type | Digital |
Voltage | 24 V |
Product Brand | ABB |
Series | S800 |
Current | 2 A |
The DO815 is a 8 channel 24 V digital output module for the S800 I/O. The output voltage range is 10 to 30 V and the maximum continuous output current is 2 A @ 24 V. The outputs are protected against short circuits, and over load. The outputs are divided into two individually isolated groups with four output channels in each group. Each output channel consists of a short circuit and over load protected high side driver with open load detection (on active signal), EMC protection components, inductive load suppression, output status indication LEDs and optical isolation barrier.
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DO801 / 3BSE020510R1 |
The DO801 is a 16 channel 24 V digital output module for the S800 I/O. The output voltage range is 10 to 30 volt and the maximum continuous output current is 0.5 A. The outputs are protected against short circuits, over voltage and over temperature. The outputs are in one isolated group. Each output channel consists of a short circuit and over temperature protected high side driver, EMC protection components, inductive load suppression, output state indication LED and optical isolation barrier.
Features and benefitsArticle number | 3BSE020510R1 |
Type | Digital Output |
Signal specification | 24 V d.c. (12 - 32 V d.c.), 0.5 A |
Number of channels | 16 |
Signal type | Current sourcing, current limiting |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800L |
Isolation | Groupwise isolated from ground |
Output load | < 0.4 Ω |
Current limiting | Short circuit proof current limited output |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 2.1 W |
Current consumption +5 V Modulebus | 80 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 0 |
Supported wire size | Solid: 0.05-2.5 mm², 30-12 AWG Stranded: 0.05-1.5 mm², 30-12 AWG Recommended torque: 0.5-0.6 Nm Stripping length 6-7.5mm, 0.24-0.30 inch |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI801 / 3BSE020512R1 |
The AI801 Analog Input Module has 8 channels for current input. The current input is able to handle a short circuit to the transmitter supply at least 30 V d.c without damage.
Current limiting is performed with a PTC resistor. The input resistance of the current input is 250 ohm, PTC included.
Features and benefitsArticle number | 3BSE020512R1 |
Type | Analog Input |
Signal specification | 0...20 mA, 4...20 mA |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800L |
Resolution | 12 bit |
Input impedance | 230 - 275 kΩ (current input incl PTC) |
Isolation | Groupwise isolated from ground |
Under/over range | 0% / +15% |
Error | Max 0,1% |
Temperature drift | Typ. 50 ppm/°C, Max. 80 ppm/°C |
Input filter (rise time 0-90%) | 180 ms |
Update cycle time | 1 ms |
Maximum field cable length | 600 meters (656 yards) |
Max input voltage (non destructive) | 30 V d.c. |
NMRR, 50Hz, 60Hz | > 40dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 1.1 W |
Current consumption +5 V Modulebus | 70 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 30 mA |
Supported wire size | Solid: 0.05-2.5 mm², 30-12 AWG Stranded: 0.05-1.5 mm², 30-12 AWG Recommended torque: 0.5-0.6 Nm Stripping length 6-7.5mm, 0.24-0.30 inch |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AI820 / 3BSE008544R1 |
The AI820 Analog Input Module has 4 differential, bipolar current/voltage inputs. Each channel can be either a voltage or current input. The current inputs can withstand an accidental maximum normal mode 30 V d.c. connection. To protect the current input circuit against dangerous input levels, that is, by accidentally connecting a 24 V source, the resistor rating of the 250W current sense resistors is about 5 Watts. This is intended only to temporarily protect one channel at a time.
The module distributes the external transmitter supply to each channel. This adds a simple connection (with extended MTUs) to distribute the supply to external 2 wire transmitters. There is no current limiting on the transmitter power terminals.
All 4 channels are isolated from the ModuleBus in one group. Power to the input stages is converted from the 24 V on the ModuleBus.
Features and benefitsArticle number | 3BSE008544R1 |
Type | Analog Input |
Signal specification | -20..+20 mA, 0(4)..20 mA, -10..+10 V, 0(2)..10 V |
Number of channels | 4 |
Signal type | Bipolar differential |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 14 bit plus sign |
Input impedance | 200 kΩ ± 25% (voltage mode, common mode) 800 kΩ ± 25% (voltage mode, normal mode) 250 Ω (current input) |
Isolation | Groupwise isolated from ground (RIV=50 V) |
Under/over range | ± 15% |
Error | Max. 0.1% |
Temperature drift | Voltage: Max. 70 ppm/°C Current: Max. 50 ppm/°C |
Input filter (rise time 0-90%) | 40 ms |
Current limiting | Transmitter power can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 1.7 W |
Current consumption +5 V Modulebus | 80 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 70 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Analog |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | AO815 / 3BSE052605R1 |
The AO815 Analog Output Module has 8 unipolar analog output channels. The module performs self-diagnostic cyclically. Module diagnostics include:
The module has HART pass-through functionality. Only point to point communication is supported. The output filter must be enabled on channels used for HART communication.
Features and benefitsArticle number | 3BSE052605R1 |
Type | Analog Output |
Signal specification | 4..20 mA |
Number of channels | 8 |
HART | Yes |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Resolution | 12 bit |
Isolation | Groupwise isolated from ground |
Under/over range | -12.5% / +15% |
Output load | Max 750 Ω |
Error | Max. 0.1% |
Temperature drift | Max. 50 ppm/°C |
Input filter (rise time 0-90%) | 23 ms (0-90%), max 4 mA / 12.5 ms |
Update cycle time | 10 ms |
Current limiting | Short circuit proof current limited output |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 3.5 W (typ.) |
Current consumption +5 V Modulebus | Max. 125 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | Max. 165 mA |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DI821 / 3BSE008550R1 |
The DI821 is a 8 channel, 230 V a.c./d.c, digital input module for the S800 I/O. This module has 8 digital inputs. The ac input voltage range is 164 to 264 V and the input current is 11 mA at 230 V a.c. The d.c. input voltage range is 175 to 275 volt and the input current is 1.6 mA at 220 V d.c. The inputs are individually isolated.
Every input channel consists of current limiting components, EMC protection components, input state indication LED, optical isolation barrier and an analog filter (6 ms).
Channel 1 can be used as voltage supervision input for channels 2 - 4, and channel 8 can be used as voltage supervision input for channels 5 - 7. If the voltage connected to channel 1 or 8 disappears, the error inputs are activated and the Warning LED turns on. The error signal can be read from the ModuleBus.
Features and benefitsArticle number | 3BSE008550R1 |
Type | Digital Input |
Signal specification | 230 V a.c., 220 V d.c. |
Number of channels | 8 |
Signal type | Current sinking |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Input voltage range, "0" | 0..50 V a.c., 0..40 V d.c. |
Input voltage range, "1" | 164..264 V a.c., 175..275 V d.c. |
Input impedance | 21 kΩ (a.c.) / 134 kΩ (d.c.) |
Isolation | Individually isolated channels |
Filter times (digital, selectable) | 2, 4, 8, 16 ms |
Input frequencey range | 47..63 Hz |
Analog filter On/Off delay | 5 / 28 ms |
Current limiting | Sensor power can be current limited by the MTU |
Maximum field cable length | 200 meters (219 yards) 100 pF/m for a.c., 600 meters (656 yards) for d.c. |
Rated insulation voltage | 250 V |
Dielectric test voltage | 2000 V a.c. |
Power dissipation | Typ. 2.8 W |
Current consumption +5 V Modulebus | 50 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details
Minimum Order Quantity: 1 Piece
Product Brochure
Manufacturer Series | AC800M |
Mounting Type | DIN Rail |
Output Type | Digital |
Pulse Transmission Output | 1 |
Communication Port | 1 |
MODEL | DI810 / 3BSE008508R1 |
This module has 16 digital inputs. The input voltage range is 18 to 30 volt d.c. and the input current is 6 mA at 24 V. The inputs are divided into two individually isolated groups with eight channels and one voltage supervision input in each group. Every input channel consists of current limiting components, EMC protection components, input state indication LED and optical isolation barrier. The process voltage supervision input give channel error signals if the voltage disappears. The error signal can be read via the ModuleBus.
Features and benefitsArticle number | 3BSE008508R1 |
Type | Digital Input |
Signal specification | 24 V d.c. |
Number of channels | 16 |
Signal type | Current sinking |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Input voltage range, "0" | -30..+5 V |
Input voltage range, "1" | 15..30 V |
Input impedance | 3.5 kΩ |
Isolation | Groupwise isolated from ground, 2 groups with 8 channels |
Filter times (digital, selectable) | 2, 4, 8, 16 ms |
Current limiting | Sensor power can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 1.8 W |
Current consumption +5 V Modulebus | 50 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 0 |
Additional Information:
View Complete details